YES
|
NO
|
N/A
|
|
|
|
|
|
|
|
A.
|
|
Contract Plans, Specifications, Permits, etc.
|
|
|
|
|
|
|
|
|
|
|
|
|
1.
|
Are the shoring plans prepared, stamped, and signed by an engineer registered to practice in Oregon?
|
|
____
|
____
|
____
|
|
|
|
|
|
|
|
|
2.
|
Have three copies (five copies if railroad approval is required) of the complete design calculations accompanied the shoring drawings submittal?
|
|
____
|
____
|
____
|
|
|
|
|
|
|
|
|
3.
|
Are shoring plans in compliance with the requirements of the construction plans general notes?
|
|
____
|
____
|
____
|
|
|
|
|
|
|
|
|
4.
|
Are shoring plans in compliance with contract plan structural details?
|
|
____
|
____
|
____
|
|
|
|
|
|
|
|
|
5.
|
Are shoring plans in compliance with the requirements of the Oregon Standard Specifications for Construction, subsection 00150.35?
|
|
____
|
____
|
____
|
|
|
|
|
|
|
|
|
6.
|
Are all existing, adjusted or new utilities in proximity with the proposed shoring shown on the shoring plans and is protection of these utilities addressed?
|
|
____
|
____
|
____
|
|
|
|
|
|
|
|
|
7.
|
Are clearance requirements satisfied and shown on the shoring plans?
|
|
____
|
____
|
____
|
|
|
|
|
|
|
|
B.
|
|
Loads
|
|
|
|
|
|
|
|
|
|
|
|
|
1.
|
Are the magnitude and location of all loads, equipment and personnel that will be supported by the shoring shown or noted on the shoring plans?
|
|
____
|
____
|
____
|
|
|
|
|
|
|
|
|
2.
|
Are design loads and material properties used to determine design stresses shown for each different shoring member shown on the shoring plans?
|
|
____
|
____
|
____
|
|
|
|
|
|
|
|
|
3.
|
Does the shoring design assume water saturated soil pressure acts on the full height of the shoring?
|
|
____
|
____
|
____
|
|
|
|
|
|
|
|
|
4.
|
Has percolation into the excavation been addressed?
|
|
____
|
____
|
____
|
|
|
|
|
|
|
|
C.
|
|
Allowable Stresses
|
|
|
|
|
|
|
|
|
|
|
|
|
1.
|
Have the design loads used for shoring design of all members been noted in the design calculations?
|
|
____
|
____
|
____
|
|
|
|
|
|
|
|
|
2.
|
Are the allowable stress and the calculated stress listed in the summary for each different shoring member?
|
|
____
|
____
|
____
|
|
|
|
|
|
|
|
D.
|
|
Timber Construction
|
|
|
|
|
|
|
|
|
|
|
|
|
1.
|
Are timber grades consistent with material to be delivered to the construction site and noted on shoring drawings and in accompanying calculations for all timber shoring material?
|
|
____
|
____
|
____
|
|
|
|
|
|
|
|
|
2.
|
If "rough" lumber is specified for shoring by the shoring designer are the actual lumber dimensions used in calculations shown?
|
|
____
|
____
|
____
|
|
|
|
|
|
|
|
E.
|
|
Steel Construction
|
|
|
|
|
|
|
|
|
|
|
|
|
1.
|
Are steel structural shapes and plates identified by ASTM number on the shoring plans and in the calculations?
|
|
____
|
____
|
____
|
|
|
|
|
|
|
|
|
2.
|
Have steel beams been checked for bending, shear, web crippling and buckling of the compression flange?
|
|
____
|
____
|
____
|
|
|
|
|
|
|
|
F.
|
|
Compression Members, Bracing, Members
and Connections
|
|
|
|
|
|
|
|
|
|
|
|
1.
|
Has general buckling been evaluated for all compression members?
|
|
____
|
____
|
____
|
|
|
|
|
|
|
|
|
2.
|
Has bracing been provided at all points of assumed support for compression members?
|
|
____
|
____
|
____
|
|
|
|
|
|
|
|
|
3.
|
Is bracing strength and stiffness sufficient for the intended purpose?
|
|
____
|
____
|
____
|
|
|
|
|
|
|
|
|
4.
|
Have all connections been designed and detailed?
|
|
____
|
____
|
____
|